Overview
NIBE FIGHTER 1240 is a ground source heat pump
for heating single and small multi family homes.
They incorporate a 160 litre hot water cylinder
and immersion boost heaters. You hot water needs
will be assessed by us on system design, with
most 3 - 4 bedroom houses ideally suited for the
1240 ground source heat pump.

Single Phase
| NIBE
Fighter 1240 Ground Source Heat Pump |
5
KW |
8
KW |
12
KW |
| Recorded Capacity*
(Brine O /W 35) |
1.0 KW |
1.8 KW |
2.5 KW |
| Emitted Capacity* (Brine O /W 35) |
4.8 KW |
8.3 KW |
11.5 KW |
| CoP at Brine 0 /W
35 |
4.6 CoP |
4.6 CoP |
4.6 CoP |
| Height |
1890 mm |
1890 mm |
1890 mm |
| Width |
600mm |
600mm |
600mm |
| Depth |
625mm |
625mm |
625mm |
| Net Weight |
280kg |
300kg |
310kg |
| Operating Voltage |
230 V (1-Phase+N) |
230 V (1-Phase+N) |
230 V (1-Phase+N) |
| Integrated Cartridge
Heater |
6 (6) KW |
6 (6) KW |
6 (6) KW |
| Refrigerant |
R407C |
R407C |
R407C |
| Ground Heat, hose
length** |
200-300 m |
400-2X300 m |
2x250 m-2X350 m |
| Borehole Depth for ground probe** |
70-90 m |
140-170 m |
160-190 m |
| Heating Medium Flow |
0.10 l/s |
0.19 l/s |
0.31 l/s |
| Brine Flow |
0.25 l/s |
0.53 l/s |
0.65 l/s |
| Hot Water Cylinder
Volume |
160 litres |
160 litres |
160 litres |
| Jacket Cylinder Volume |
45 litres |
45 litres |
45 litres |
* Specifications relative to 100%
QN with 1800 operating hours heater and 200 operating
hours hot water at 450 m above sea level
** Stated values are only approximate guide values,
specifications for surface collector with PE-pipe
40 x 2,3.